Introduction
5
Relay Outputs
The outputs can be connected to IS circuits with the following maximum
values:
Ui = 28V
Ii = 93mA
Pi = 653mW
The internal capacitance and inductance seen on these terminals is 0.1uF and
0mH.
Flowmeter Input
Entity parameters on the flowmeter enable connection to a wide range of
approved sensors.
Input parameters are:
Ui = 24V
Ii = 20mA
Pi = 320mW
The internal capacitance and inductance seen on these terminals is 0.002uF
and 0mH.
Output parameters are:
Uo = 10.0V
Io = 9.0mA
Maximum allowed external capacitance is 60µF.