6 Specification
2. SPECIFICATION
General
Display: 6 digit LCD. 0.7" (17.8mm) high digits.
Display Update Rate: 0.25 seconds.
Transducer Supply: 8-24VDC field adjustable.
50mA maximum.
Power Requirements: 11.5 to 28.5 volts DC.
130mA typical current (no options).
AC Mains: Set internally to 95 - 135 VAC or
190 - 260 VAC.
Operating Temperature: 0 to 55°C standard.
Dimensions: 5.7" (144mm) wide x 2.8" (72mm) high x
7.0" (178mm) deep.
Cutout: 5.5" (139mm) wide x 2.6" (67mm) high.
Frequency Input
Frequency Range: Minimum: 0.25Hz on Rate.
0Hz on Total.
Maximum: 10KHz.
Input Circuits: See Sections 6.1 and 6.2.
Scaling Range: 0.1000 to 50,000.
Relay Outputs
Maximum Switching Power: 1250VA.
Maximum Switching Voltage: 250VAC, 30VDC.
Maximum Switching Current: 5 Amps.
Vedere la pagina 7